55
Controlling Data Links
Section 4-8
Node 6 Table
Node 8 Table
4-8
Controlling Data Links
It is necessary to start the data links after finishing the data link settings.
Starting the data links is carried out by any one of the following three startup
operations. This is true for both manual settings and automatic settings.
• From the DM parameter software switches
• By sending a command
• By using the Support Software
Note
(1) The data link mode (manual settings or automatic settings) and the data
link system are determined by the data link settings for the startup node.
(2) Be sure to set the data link mode (manual settings) and the data link table
in the DM parameter area of the startup node when using manual set-
tings.
(3) Be sure to set the data link mode (automatic settings) and the number of
data link words in the DM parameter area of the startup node when using
automatic settings.
(4) The data links will not operate unless the settings are correct.
Refresh param-
eters
PLC type
Select “CV/CVM1”
Start word
CIO
CIO Area local node data link start address:
CIO 1000
DM
DM Area local node data link start address:
D00020
Refresh nodes
Node refresh order: 2, 5, 6
Item
Setting
Item
Setting
Node address
Local node address: 6
Common link
parameters
Number of words in
CIO Area
CIO Area local node send size: 5 words
Number of words in
DM Area
DM Area local node send size: 5 words
Refresh param-
eters
PLC type
Select “CV/CVM1”
Start word
CIO
CIO Area local node data link start address:
CIO 1005
DM
DM Area local node data link start address:
D00000
Refresh nodes
Node refresh order: 5, 6
Item
Setting
Node address
Local node address: 8
Common link
parameters
Number of words in
CIO Area
CIO Area local node send size: 0 words
(nothing set)
Number of words in
DM Area
DM Area local node send size: 5 words
Refresh param-
eters
PLC type
Select “CV/CVM1”
Start word
CIO
CIO Area local node data link start address:
CIO 1010
DM
DM Area local node data link start address:
D00000
Refresh nodes
Node refresh order: 6, 2, 5, 8
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...