146
Replacing the Unit
Section 9-1
9-1
Replacing the Unit
Observe the following precautions when replacing the Unit.
• Always turn OFF the power before replacing the Unit.
• Check that the new Unit is not faulty.
• If you suspect that a poor connection is the cause of a malfunction, clean
the connectors using a clean, soft cloth and industrial-grade alcohol.
Remove any lint or threads left from the cloth, and remount the Unit.
• When returning a faulty Unit for repairs, always attach a detailed fault
report to the Unit and return to you nearest OMRON outlet as listed at the
back of this manual.
Note
(1) To prevent faulty operation be sure to turn OFF the power to all nodes be-
fore replacing the Unit.
(2) When replacing the Unit, do not reconnect that node to the Network be-
fore carrying out the procedures listed below. In particular, a node with a
small address will become the polling node and communicate the initial
network parameter status to other nodes, so there is the chance that net-
work parameters in the entire Network will be damaged.
9-1-1
Settings after Replacement
After replacing a SYSMAC LINK Unit, reset the hardware switches, software
switches, and data link tables, and wire it in the same manner as the previous
Unit. This section describes settings that require particular care. Refer to the
Unit replacement methods later in this section for details on replacing the Unit.
Note
(1) After replacing the CPU Unit, transfer important data, such as DM and
Holding Area contents, to the new CPU Unit before restarting operation.
Depending on the program, accidents can occur as a result of incorrect
DM or Holding Area contents.
(2) CS-series SYSMAC LINK Units store data such as data link tables, net-
work parameters, and routing tables in the CPU Unit. When replacing the
CPU Unit, reset these settings using the CX-Net in CX-Programmer.
9-1-2
Resetting Network Parameters
When a CPU Unit has been replaced in a CS-series SYSMAC LINK Unit, it is
necessary to reset the network parameters, data link tables, and routing
tables. This section describes the resetting procedure for the network param-
eters. For details on data link table resetting procedures, refer to
4-5 Creating
Data Links
and for routing table resetting procedures, refer to
5-2 Routing
Tables
.
1,2,3...
1.
Network parameters are read from the polling node when the Network is
activated and this information is distributed to all nodes in the Network. For
this reason, set the polled/polling node setting in the DM parameter area
for the node replaced to a polled node before reconnecting the Unit to the
SYSMAC LINK Network.
2.
Turn the power OFF once, connect the SYSMAC LINK Network and turn
the power ON again. Check that the Unit is participating in the Network.
0: Polling node
1: Polled node
Polled node/polling node
−
: Other settings
DM 30000 + 100
×
n
n = Unit number
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...