67
CX-Programmer Procedures
Section 4-12
Minimum Data Link I/O Response Time
4-12 CX-Programmer Procedures
This section describes the procedures from creation of data link tables to
starting up data links using CX-Net in CX-Programmer.
Here, the procedure for CX-Net in CX-Programmer Ver. 1.2 (Service Pack 1)
is given as an example. The operations, windows, and setting items may vary
with the version of CX-Programmer.
4-12-1 Overall Procedure
If building SYSMAC LINK data links for the first time, make the settings using
the following procedure. It is necessary to create data link tables if using man-
ually set data links.
Note
There is no need to create data link tables when using automatic settings. If
using automatically set data links, set the DM parameter areas (DM area
words allocated to the SYSMAC LINK Unit as a CPU Bus Unit) using a Pro-
gramming Console or the PLC Memory Window in CX-Programmer.
1,2,3...
1.
Start CX-Net from the CX-Programmer by selecting
Tools
and then
Net-
work Configuration Tool
.
2.
Open the CX-Server file (*.CDM) in CX-Net or create a new file in CX-Net
by selecting
Project
and then
Open
in CX-Net.
3.
Start the Data Link Editor to create the data link tables by selecting
Data
Link
and then
Editor
.
• If creating the same data link tables in all nodes, start the Data Link
Engineer from the Data Link Editor by selecting
Table
and then
Data
Link Engineer
.
• If creating different data link tables for each node, create data link pa-
rameters for each node by editing tables for each node individually.
Input ON response time
---
Scan time for PLC 1
25 ms
Communications cycle time
---
Scan time for PLC 7
10 ms
Output ON response time
---
Total (data link I/O response time)
35 ms
Scan time for PLC 1
Communications cycle
Scan time for PLC 7
Output
Maximum transmission delay time
Input
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...