141
Error Log
Section 8-2
0117
Hex
Internal buffer full
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Source Network address
Bit 15:
OFF
Response block
Bits 0 to 7:
Destination node address
Bits 8 to 14:
Destination Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
Increase number of retries or
reconfigure system to distrib-
ute load.
No
0118
Hex
Illegal packet discarded
Check for nodes sending ille-
gal packets.
Yes
0206
Hex
Number of participating nodes
decreased (local node still partic-
ipating)
Network
parameters
maximum
node address
Number of
non-partici-
pating nodes
Check network parameters,
node participation, cables,
and terminating resistance.
No
0207
Hex
Number of participating nodes
decreased (local node not partic-
ipating)
No
0208
Hex
Polling node changed
Address of
previous poll-
ing node
Address of
new polling
node
Check previous polling node.
No
0209
Hex
Network parameter disagree-
ment error
00 Hex
Address of
polling node
Using the CX-Net, check net-
work parameters.
Yes
020C
Hex
Time out with token
00 Hex
Error status
(see note)
Check network parameters,
node participation, cables,
and terminating resistance.
No
0210
Hex
Communications controller send
error
00 Hex
Error status
(see note)
Replace the SYSMAC LINK
Unit.
Yes
0211
Hex
Duplicate address error
00 Hex
Local node
address
Set so that each node
address is used only once
within the same Network.
No
0214
Hex
Node address setting error
Not specified
Check the node address set-
tings and correct them.
Yes
0216
Hex
Backup power supply error (Opti-
cal Units only)
00 Hex fixed
Backup
power sup-
ply error dis-
tinction:
01 Hex: OFF
to ON
02 Hex: ON
to OFF
Check the status of the
backup power supply and
power supply cables.
Yes
021A
Hex
Set table logic error
00 Hex
01 Hex: Net-
work param-
eters
02 Hex:
Data link
tables
03 Hex:
Routing
tables
Remake and set the appropri-
ate data.
Yes
021B
Hex
Hardware error
00 Hex
Error status
(see note)
Replace the SYSMAC LINK
Unit.
No
Error
code
Contents
Detail code
Correction
Written to
EEPROM
1st byte
2nd byte
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...