114
FINS Commands for SYSMAC LINK Units
Section 6-4
Parameters
Status (response):
The operating status of the data links as follows:
00:
Stopped
01:
Active
Status 1 (response):
Communications test status as follows:
Status 2 (response):
Line status as follows:
Status 3 (response):
Error status as follows:
Note
The registered network parameters are compared to the actually network
parameters upon power application the first time a Unit joins the network. If
the parameters do not agree, bit 2, above, will be turned ON, but the system
will not stop (the actual network parameters will automatically be registered).
Status 4 (response):
The cause of communications controller errors as fol-
lows:
Status 5 (response):
Backup status as follows:
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
Bit
1: Test running; 0: test stopped
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
Bit
1: Power supplied; 0: power not supplied
7
6
5
4
3
2
1
0
0
0
0
0
0
Bit
1: Node address setting range error
1: Node address duplication error
1: Network parameter disagreement
7
6
5
4
3
2
1
0
0
0
0
Bit
1: Watchdog timer error
1: Memory error
1: Chip error
1: Transmitter error
1: Local node echo test error
7
6
5
4
3
2
1
0
0
0
0
Bit
1: Network parameter error
1: Data link table error
1: Routing table error
1: Software switch error
1: EEPROM error
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...