139
Error Log
Section 8-2
0012
Hex
CPU Unit memory error
01 Hex: Read
error
02 Hex: Write
error
01 Hex:
Data link
table
02 Hex: Net-
work param-
eters
03 Hex:
Routing
table
04 Hex: PLC
Setup Area
Set the appropriate data.
Yes
0013
Hex
CPU Unit write-protected
Release the CPU Unit write
protection.
Yes
0101
Hex
Transmission failed; local node
not in Network
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Source Network address
Bit 15:
OFF
Response block
Bits 0 to 7:
Destination node address
Bits 8 to 14:
Destination Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
Refer to page
8-1-1 Error Indi-
cations
and place the local
node into Network.
No
0103
Hex
Transmission failed; retry count
exceeded
Using the CX-Net or FINS
commands, run echoback
tests and check operating
environment if errors occur.
No
0104
Hex
Transmission failed; maximum
number of frames exceeded.
Reduce the number of events
per communications cycle or
increase the maximum num-
ber of network parameter
frames.
No
0105
Hex
Transmission failed; node
address incorrect
Check node address settings
to be sure they are within
range and unique.
No
0106
Hex
Transmission failed; redundant
node address
Correct node addresses so
that they are unique within the
same Network.
No
0107
Hex
Transmission failed; destination
node not in Network
Refer to
8-1-1 Error Indica-
tions
and place destination
node into Network.
No
0108
Hex
Transmission failed; specified
Unit does not exist
Check the unit address and
unit number of destination.
No
Error
code
Contents
Detail code
Correction
Written to
EEPROM
1st byte
2nd byte
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...