129
Troubleshooting
Section 8-1
Note
Calculate the location of the error information in the CPU Bus Unit as follows:
CIO 1500 + unit number x 25 + 1 word.
Lit
---
Lit
---
Bit 15 (error log infor-
mation) is ON.
0001
Hex
CPU Unit error.
Refer to the PLC operation
manual, and clear the error. If
the error reoccurs, replace
the CPU Unit.
Both bit 00 (network
parameter error) and
bit 15 (error log infor-
mation) are ON.
0012
Hex
CPU Bus Unit set-
tings area network
parameters data is
corrupted.
Correct the network parame-
ters. If the error reoccurs,
replace the PLC CPU Unit.
021A
Hex
Network parameter
settings contain an
error, or the local
node address
exceeds the network
parameters maxi-
mum node address.
Correct the network parame-
ters correctly.
Both bit 01 (data link
table error) and bit 15
(error log informa-
tion) are ON.
0012
Hex
PLC Bus Unit system
settings area data link
tables data is cor-
rupted.
Correct the data link tables. If
the error reoccurs, replace
the PLC CPU Unit.
021A
Hex
The data link table
settings contain an
error.
Correct the data link tables,
or delete the data link tables
if not using them.
Both bit 02 (routing
table error) and bit 15
(error log informa-
tion) are ON.
0012
Hex
PLC parameter area
routing tables data is
corrupted.
Reset the routing tables. If
the error reoccurs, replace
the PLC CPU Unit.
021A
Hex
The routing table set-
tings contain an error.
Correct the routing tables, or
delete the routing tables if
not using them.
Lit
---
---
Not lit
---
---
Terminating resistors
are not mounted cor-
rectly (coaxial only).
Mount terminating resistors
on both end nodes of the
SYSMAC LINK network.
---
---
The cable is not con-
nected correctly.
Connect the cable connec-
tions, then reconnect the
cable correctly.
---
---
Node address
exceeds network
parameters maxi-
mum node address.
Either correct the network
parameters maximum node
address using CX-Net in CX-
Programmer, or set the node
address to within the maxi-
mum node address.
---
---
No other nodes exist.
Be sure that there are a mini-
mum of two active nodes in
the network.
---
---
No node is set as the
polling node.
Set a Unit as the polling
node.
Indicators
CPU Bus Unit CIO
Area error
information
Error
log
Probable cause
Remedy
RUN
ERC
ERH
INS
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...