3. SIGNALS AND WIRING
3 - 62
(1) Connection diagram
B2
B1
MBR
DOCOM
RA1
U
B
Servo motor
24 V DC
ALM
(Malfunction)
Servo amplifier
MBR
RA1
(Note 1)
(Note 2)
24 V DC
Note 1. Create the circuit in order to shut off by interlocking with the emergency stop switch.
2. Do not use the 24 V DC interface power supply for the electromagnetic brake.
(2) Setting
(a) Enable MBR (Electromagnetic brake interlock) with [Pr. PD03] to [Pr. PD20].
(b) In [Pr. PC16 Electromagnetic brake sequence output], set a delay time (Tb) from MBR
(Electromagnetic brake interlock) off to base circuit shut-off at a servo-off as in the timing chart in
section 3.10.2 (1).