5. PARAMETERS
5 - 39
No./symbol/
name
Setting
digit
Function
Initial
value
[unit]
Control mode
P S T
PC73
ERW
Error
excessive
warning level
Set an error excessive warning level.
To enable the parameter, select "Enabled (1 _ _ _)" of "[AL. 9B Error excessive
warning] selection" in [Pr. PC60].
You can change the setting unit with "Error excessive alarm/error excessive warning
level unit selection" in [Pr. PC24].
Set the level in rev unit. When "0" is set, 1 rev will be applied. Setting over 200 rev
will be clamped with 200 rev.
When an error reaches the set value, [AL. 9B Error excessive warning] will occur.
When the error decreases lower than the set value, the warning will be canceled
automatically. The minimum pulse width of the warning signal is 100 [ms].
Set as follows: [Pr. PC73 Error excessive warning level] < [Pr. PC43 Error excessive
alarm level] When you set as [Pr. PC73 Error excessive warning level] ≥ [Pr.
PC43
Error excessive alarm level], [AL. 52 Error excessive] will occur earlier than the
warning.
This parameter setting is available with servo amplifiers with software version B4 or
later.
Setting range: 0 to 1000
0
[rev]
Summary of Contents for MR-JE-_A
Page 9: ...A 8 MEMO ...
Page 15: ...6 MEMO ...
Page 29: ...1 FUNCTIONS AND CONFIGURATION 1 14 MEMO ...
Page 139: ...4 STARTUP 4 38 MEMO ...
Page 187: ...5 PARAMETERS 5 48 MEMO ...
Page 221: ...6 NORMAL GAIN ADJUSTMENT 6 34 MEMO ...
Page 259: ...8 TROUBLESHOOTING 8 8 MEMO ...
Page 265: ...9 DIMENSIONS 9 6 MEMO ...
Page 273: ...10 CHARACTERISTICS 10 8 MEMO ...
Page 339: ...12 COMMUNICATION FUNCTION MITSUBISHI ELECTRIC GENERAL PURPOSE AC SERVO PROTOCOL 12 34 MEMO ...