4. STARTUP
4 - 32
4.5.8 Output signal (DO) forced output
POINT
When the servo system is used in a vertical lift application, turning on MBR
(Electromagnetic brake interlock) by the DO forced output after assigning it to
connector CN1 will release the electromagnetic brake, causing a drop. Take
drop preventive measures on the machine side.
Output signals can be switched on/off forcibly independently of the servo status. Use this function for output
signal wiring check, etc. This operation must be performed in the servo off state by turning off SON (Servo-
on).
Operation
The display screen at power-on. Using the "MODE" button, display the diagnostic screen.
……
……
……
……
……
Switch on/off the signal below the lit segment.
Indicates on/off of output signal. Definitions of on/off
are the same as those for the external I/O signals.
(Light on: on, light off: off)
Press "UP" three times.
Press "SET" for longer than 2 s.
CN1
33
CN1
48
CN1
23
CN1
24
CN1
49
Press "MODE" once.
Press "UP" once.
CN1-24 switches on.
(Between CN1-24 and DOCOM are connected.)
The lit LED moves to the upper LED of CN1-24.
Press "DOWN" once.
CN1-24 switches off.
Press "SET" for longer than 2 s.
Always lit.
Summary of Contents for MR-JE-_A
Page 9: ...A 8 MEMO ...
Page 15: ...6 MEMO ...
Page 29: ...1 FUNCTIONS AND CONFIGURATION 1 14 MEMO ...
Page 139: ...4 STARTUP 4 38 MEMO ...
Page 187: ...5 PARAMETERS 5 48 MEMO ...
Page 221: ...6 NORMAL GAIN ADJUSTMENT 6 34 MEMO ...
Page 259: ...8 TROUBLESHOOTING 8 8 MEMO ...
Page 265: ...9 DIMENSIONS 9 6 MEMO ...
Page 273: ...10 CHARACTERISTICS 10 8 MEMO ...
Page 339: ...12 COMMUNICATION FUNCTION MITSUBISHI ELECTRIC GENERAL PURPOSE AC SERVO PROTOCOL 12 34 MEMO ...