[8-10 Troubleshooting Inverter Problems ]
50
-
chapter 8
BS_08_E
8 Troub
le
sho
oting Bas
ed on Ob
ser
ved
Sy
mp
toms
8-10-14
Checking the Pump INV Board for Damage (During pump operation)
8-10-15
Checking the Installation Conditions
8-10-16
Solutions for the Main Breaker Trip
Items to be checked
Phenomena
Remedy
Operate the outdoor unit and the
hydro unit.
Wait until the inverter output frequen-
cy is stabilized, and then check the
inverter output voltage.
1)
Overcurrent-related error occurs im-
mediately after the startup of the
pump or during operation of the
pump.
Check code: 4250
Detail code: 101, 102, 103, 106, 107
a. Check that the results of the
check items in [8-10-11 Checking
the Pump Motor for Ground Fault
and Coil Resistance Problems]
through [8-10-13 Checking the
Pump INV Board for Damage
(Without load)] are OK.
→
If the error persists after sever-
al compressor restarts, go to "b."
b. After the startup of the compres-
sor, check the high and low pres-
sures for a proper differential
pressure. (Water pressure)
If a proper differential pressure
does not exist, replace the pump.
(The pump may be locked.)
2)
After the inverter output voltage is
stabilized, line voltage imbalance of
at least 5% or 5 V occurs.
If line voltage imbalance exists:
<INV32>
Replace the INV board.
Items to be checked
Phenomena
Remedy
(1)
Check refrigerant charge.
Overcharge of refrigerant
Return to correct refrigerant
charge.
(2)
Check outdoor unit branch in-
stallation.
The branch approach <500 mm.
Make branch approach >500mm
Is the branch angle < ±15° to horizontal? Make branch angle < ±15°
Items to be checked
Phenomena
Remedy
[1]
Check the breaker capacity.
Use of a non-specified break-
er
Replace it with a specified breaker.
[2]
Perform Meg check between the
terminals on the power terminal
block TB1.
Zero to several ohm, or Meg
failure
Check each part and wiring.
Refer to the following page(s). [8-10-18
Simple Check on Inverter Circuit Compo-
nents]
IGBT module
Rush current protection resistor
Electromagnetic relay
DC reactor
[3]
Turn on the power again and
check again.
1)
Main power breaker trip
2)
No remote control display
[4]
Turn on the outdoor unit and check
that it operates normally.
1)
Operates normally without
tripping the main breaker.
a) The wiring may have been short-circuit-
ed. Search for the wire that short-circuit-
ed, and repair it.
b) If item a) above is not the cause of the
problem, refer to [8-10-2 Checking the
Inverter Board Error Detection Circuit] -
[8-10-10 Checking the Fan Board for
Damage with Load]
2)
Main power breaker trip
0000004986.BOOK 50 ページ 2019年5月9日 木曜日 午後6時22分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......