[7-7 Error Code Definitions and Solutions: Codes [5000 - 5999] ]
BS_07_E
chapter 7 -
53
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-7-4
Error Code [5111, 5113, 5132, 5135]
1. Error code definition
5111 - 5113
Temperature sensor fault (Hydro unit) (TH11, TH13)
5132 - 5135
Temperature sensor fault (Hydro unit) (TH32, TH35)
2. Error definition and error detection method
If a shorted (high temperature intake) or open (low temperature intake) thermistor (TH11, TH13, TH32, TH35) is detected
during operation, the unit comes to an abnormal stop, and an error code “5111,” “5113,” “5132,” “5135” appears on the display.
Detection of a short- or open-circuit as described above is suspended during the defrost cycle and for 3 minutes after the
operation mode is changed.
3. Cause, check method and remedy
<Reference>
7-7-5
Error Code [5120]
1. Error code definition
DCL temperature sensor circuit fault (Detail code 01)(outdoor unit)
2. Error definition and error detection method
When an open phase or a short circuit of the temperature sensor is detected immediately before inverter startup or during
operation (applicable to INV37YC only)
3. Cause, check method and remedy
INV37YC
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems]
Cause
Check method and remedy
(1)
Thermistor failure
Check thermistor resistance.
(2)
Pinched lead wire
Check for pinched lead wire.
(3)
Torn wire coating
Check for wire coating.
(4)
A pin on the male connector is missing or
contact failure
Check connector.
(5)
Disconnected wire
Check for wire.
Short detection
Open detection
TH11
110°C [230°F] and above (0.4k
Ω
)
-40°C [-40°F] and below (130k
Ω
)
TH13
110°C [230°F] and above (0.4k
Ω
)
-40°C [-40°F] and below (130k
Ω
)
TH32
110°C [230°F] and above (0.4k
Ω
)
-40°C [-40°F] and below (130k
Ω
)
TH35
110°C [230°F] and above (0.4k
Ω
)
-40°C [-40°F] and below (130k
Ω
)
Cause
Check method and remedy
(1)
Contact failure
Check the connector (CNTH) on the inverter board for proper
connection.
(2)
DCL temperature sensor
Disconnect the connector (CNTH), check the resistance val-
ue of the DCL temperature sensor.
Replace the DCL if the resistance is as follows: 0.5 k
Ω
or be-
low (short-circuit) or 1963 k
Ω
or above (open-circuit).
(3)
INV board failure
If the problem persists after restart operation, replace the in-
verter board.
0000004984.BOOK 53 ページ 2019年5月17日 金曜日 午前8時21分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......