[6-1 Read before Test Run ]
BS_06_E
chapter 6 -
1
6 Tes
t Ru
n
6 Test Run
6-1
Read before Test Run
(1) Check for refrigerant leak and loose cables and connectors.
(2) When opening or closing the front panel of the control box, do not let it come into contact with
any of the internal components.
Before inspecting the inside of the control box, turn off the power, leave the unit turned off for at least 10 minutes, and check
that the voltage across pins 1 and 5 of connector RYPN has dropped to 20 VDC or less. (It takes approximately 10 minutes
to discharge electricity after the power is turned off.)
Control box houses high temperature parts. Be well careful even after turning off the power source.
Disconnect the relay connectors (RYFAN 1 and RYFAN 2) on the outdoor unit fan before performing maintenance work. (Be-
fore connecting or disconnecting the connector, check that the outdoor unit fan is stopped and that the voltage across pins 1
and 5 of connector RYPN has dropped to 20 VDC or less. If the outdoor unit fan is turned by strong winds, the main circuit
capacitor will be energized and poses an electric shock hazard. Refer to the wiring diagram name plate for details.
To connect wiring to TB7, check that the voltage is 20 VDC or below.
Reconnect the relay connectors (RYFAN 1 and RYFAN 2) on the outdoor unit fan after completion of maintenance work.
(3) Measure the insulation resistance between the power supply terminal block and the ground
with a 500V megger and make sure it reads at least 1.0Mohm.
Do not operate the unit if the insulation resistance is below 1.0Mohm.
Do not apply megger voltage to the terminal block for transmission line. Doing so will damage the controller board.
The insulation resistance between the power supply terminal block and the ground could go down to close to 1Mohm imme-
diately after installation or when the power is kept off for an extended period of time because of the accumulation of refrigerant
in the compressor.
If insulation resistance is 1 M
Ω
or below, by turning on the main power and keeping it on for at least 12 hours, the refrigerant
in the compressor will evaporate and the insulation resistance will go up.
Do not measure the insulation resistance of the terminal block for transmission line for the unit remote controller.
(4) When the power is turned on, the compressor is energized even while it is not operating.
Before turning on the power, disconnect all power supply wires from the compressor terminal block, and measure the insula-
tion resistance of the compressor.
Check the compressor for a ground fault. If the insulation resistance is 1.0 M
Ω
or below, connect all power supply wires to
the compressor and turn on the power to the outdoor unit. (The liquid refrigerant in the compressor will evaporate by energiz-
ing the compressor.)
Make sure both the gas and liquid valves are fully opened.
(5) Check the phase sequence and the voltage of the power supply.
When the voltage is out of the ±10% range, or when the phase voltage difference is more than 2%, please discuss the coun-
termeasure with the customer.
(6) [When a transmission booster is connected]
Turn on the transmission booster before turning on the outdoor units.
If the outdoor units are turned on first, the connection information for the refrigerant circuit may not be properly recognized.
In case the outdoor units are turned on before the transmission booster is turned on, perform a power reset on the outdoor
units after turning on the power booster.
(7) Turn on the main power at least 12 hours before test run.
Insufficient powering time may result in compressor damage.
(8) When a power supply unit is connected to the transmission line for centralized control(*), per-
form a test run with the power supply unit being energized. Leave the power jumper connector
on CN41 as it is (factory setting).
*Includes the cases where power is supplied to the transmission line from a system controller with a power-supply function
0000004982.BOOK 1 ページ 2019年5月8日 水曜日 午後3時4分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......