[8-3 Refrigerant Control Problems ]
10
-
chapter 8
BS_08_E
8 Troub
le
sho
oting Bas
ed on Ob
ser
ved
Sy
mp
toms
8-3
Refrigerant Control Problems
8-3-1
Units in the Cooling Mode Do Not Operate at Expected Capacity.
1. Phenomena
Although cooling operation starts with the normal remote controller display, the capacity is not enough
2. Cause, check method and remedy
Cause
Check method and remedy
1.
Compressor frequency does not rise sufficiently.
Faulty detection of pressure sensor.
Protection works and compressor frequency does
not rise due to high discharge temperature
Protection works and compressor frequency does
not rise due to high pressure
Pressure drops excessively.
(1)
Check pressure difference between the detected
pressure by the pressure sensor and the actual pres-
sure with self-diagnosis LED.
→
If the accurate pressure is not detected, check the
pressure sensor.
Refer to the following page(s). [8-5-1 Comparing the
High-Pressure Sensor Measurement and Gauge
Pressure]
Note:
Lower inlet pressure by the low pressure sensor than
the actual pressure causes insufficient capacity.
SW4 setting (SW6-10: OFF)
(2)
Check temperature difference between the evaporat-
ing temperature (Te) and the target evaporating tem-
perature (Tem) with self-diagnosis LED.
Note:
Higher Te than Tem causes insufficient capacity.
SW4 setting (SW6-10: OFF)
Note:
Protection works and compressor frequency does not
rise even at higher Te than Tem due to high discharge
temperature and high pressure.
At high discharge temperature:
Refer to the following page(s). [7-3-1 Error Code
[1102]]
At high pressure:
Refer to the following page(s). [7-3-3 Error Code
[1302] (during operation)]
High pressure sensor
Low pressure sensor
SW4
SW4
ON
1
2
3
4
5
6
7
8
9
10
ON
1
2
3
4
5
6
7
8
9
10
Evaporating temperature Te
Target evaporating temperature Tem
SW4
SW4
ON
1
2
3
4
5
6
7
8
9
10
ON
1
2
3
4
5
6
7
8
9
10
ON
1
2
3
4
5
6
7
8
9
10
The figure at left shows that the switches 1 through 5 are set to ON and 6 through 10 are set to OFF.
0000004986.BOOK 10 ページ 2019年5月9日 木曜日 午後6時22分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......