12. Installation restrictions for outdoor units
Do not install the unit where combustible gas may leak.
- If combustible gas accumulates around the unit, fire or explosion may result.
•
Provide sufficient space around the unit for effective operation, efficient air movement, and ease of access for
maintenance.
•
Note that refrigerant gas is heavier than air and will therefore tend to collect in low spots such as basements.
•
When an indoor unit that draws in outside air exits near the outdoor unit, be careful not to affect the normal
operation of the indoor unit.
•
When the amount of drain water is excessive, drain water comes out of the outdoor unit along the panel during
heating operation. Provide sufficient space around the unit.
•
R32 is heavier than air—as well as other refrigerants—so tends to accumulate at the base (in the vicinity of the
floor). If R32 accumulates around the base, it may reach a flammable concentration in case the room is small. To
avoid ignition, maintain a safe work environment by ensuring appropriate ventilation. If the refrigerant leaks in a
room or an area that has insufficient ventilation, refrain from using flames until the work environment is improved by
ensuring appropriate ventilation.
•
Do not install the outdoor unit in a basement or machinery room, where the refrigerant stagnates.
•
Install the outdoor unit in a place where at least one of the four sides is open.
•
If the unit needs to be installed in a space where all four sides are blocked, confirm that one of these situations (A,
B, or C) is satisfied.
A: Secure sufficient installation space (minimum installation area: Amin).
Install the unit in a space with an installation area of Amin or more, corresponding to the refrigerant amount
(M). (M = factory-charged refri refrigerant to be added on site)
M (kg)
Amin (m
2
)
Amin
10
112
20
223
30
334
40
445
50
556
60
667
B: Install the unit in a space with a wall height of ≤ 0.125 m.
Good
Good
Good
NG
Wall height ≤ 0.125 m
(No restrictions apply to
the refrigerant amount)
Wall height ≤ 0.125 m
0000005109.BOOK 11 ページ 2019年5月9日 木曜日 午前10時1分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......