[7-4 Error Code Definitions and Solutions: Codes [2000 - 2999] ]
18
-
chapter 7
BS_07_E
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-4-5
Error Code [2502] (Models with a float switch)
1. Error code definition
Drain pump fault
2. Error definition and error detection method
1) The immersion of sensor tip in water is detected by the ON/OFF signal from the float switch.
Submergence of the sensor
When it is detected that the float switch has been ON for 15 seconds, it is interpreted that the sensor tip is immersed in
water.
Sensor in the air
When it is detected that the float switch has been OFF for 15 seconds, it is interpreted that the sensor tip is not immersed
in water.
2) If it is detected that the float switch has been ON for 3 minutes after the immersion of the sensor tip was detected, this is con-
sidered a drain pump failure, and "2502" appears on the monitor.
The total time it takes for this error to be detected is 3 minutes and 15 seconds, including the time it takes for the first im-
mersion of the sensor tip to be detected.
3) Detection of drain pump failure is performed while the unit is stopped.
4) The following criteria are met when the criteria for the forced stoppage of outdoor unit (system stoppage) are met.
"Liquid pipe temperature-inlet temperature
≤
-10°C [-18°F]" has been detected for 30 minutes.
It is detected by the float switch that the sensor tip has been immersed in water for 15 minutes or more.
The conditions that are listed under items 1) through 3) above are always met before the criteria for the forced stoppage
of the outdoor unit.
5) The indoor unit that detected the conditions that are listed in item 4) above brings the outdoor unit in the same refrigerant
circuit to an error stop (compressor operation prohibited), and the outdoor unit brings all the indoor units in the same refrigerant
circuit that are in any mode other than Fan or Stop to an error stop. "2502" appears on the monitor of the units that came to
an error stop.
6) Forced stoppage of the outdoor unit
Detection timing: The error is detected whether the unit is in operation or stopped.
7) Ending criteria for the forced stoppage of outdoor unit
Power reset the indoor unit that was identified as the error source and the outdoor unit that is connected to the same refrig-
erant circuit.
Forced stoppage of the outdoor unit cannot be cancelled by stopping the unit via the remote controller.
(Note) Items 1) - 3) and 4) - 7) are detected independently from each other.
The address and attribute that appear on the remote controller are those of the indoor unit (or OA processing unit)
that caused the error.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Drain pump failure
Check for proper functioning of the drain pump
mechanism
(2)
Drain water drainage problem
Clogged drain pump
Clogged drain piping
Check for proper drainage.
(3)
Stuck float switch
Check for slime in the moving parts of the float switch.
Check for normal operation of the float switch.
(4)
Float switch failure
Check the resistance with the float switch turned
on and turned off.
(5)
Indoor unit control board failure
Drain pump drive circuit failure
Float switch input circuit failure
Replace indoor unit control board.
(6)
Wrong dipswitch setting on the indoor unit controller
board
Dipswitch for the new indoor unit controller board was
wrongly set to "unit model without drain pump" instead
of "unit model with drain pump" when the board was
replaced.
Check for proper dipswitch model setting on the in-
door unit controller board.
(7)
Items (1) through (5) above and an indoor unit electronic
valve closure failure (leaky valve) occurred simultane-
ously.
Check the solenoid valves on the indoor unit for
leaks.
0000004984.BOOK 18 ページ 2019年5月17日 金曜日 午前8時21分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......