[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
28
-
chapter 7
BS_07_E
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-6-4
Error Code [4114]
1. Error code definition
Indoor unit fan motor error
2. Error definition and error detection method
When the fan motor output from the indoor unit circuit board is ON and when the rotation speed input from the fan motor cannot
be detected for 30 seconds or more
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Fan motor connector contact failure
Check the fan motor connector CNMF for proper connection.
(2)
Indoor unit circuit board failure
Remove the fan motor connector CNMF and check the voltage at the
indoor unit circuit board.
Testing point 1. 280 VDC (Between CNMF1 (+) and CNMF4 (-))
2. 15 VDC (Between CNMF5 (+) and CNMF4 (-))
Replace the indoor unit circuit board if the voltage is abnormal.
If the 4114 error persists after the indoor unit circuit board is replaced,
replace the fan motor as well.
(3)
Fan motor fault
Replace the fan motor if the voltage is normal in step (2) above.
If the 4114 error persists after the fan motor is replaced, replace the in-
door unit circuit board as well.
0000004984.BOOK 28 ページ 2019年5月17日 金曜日 午前8時21分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......