[9-4 Maintenance LED Display and Troubleshooting ]
16
-
chapter 9
BS_09_C
9 USB Func
tion
(5) Maintenance LED displays "Er02."
(Meaning or Cause)
Software rewrite is suspended due to a problem with the USB memory stick during the software rewrite process.
For example, if the USB memory stick is disconnected during data storage, this display appears on the maintenance LED.
(Solution)
Check the connection of the USB memory stick.
If no problems are found, follow the procedure starting with the step explained in 1. Operation procedure (1) Starting software
rewrite mode under [9-3-2 Rewriting Software].
(6) Maintenance LED displays "Er10” or "Er11.”
(Meaning or Cause)
Because there was a problem in the control board during the software rewrite process, software rewrite has not been com-
pleted.
(Solution)
Try rewriting the software again by following the procedure detailed in 1. Operation procedure (1) Starting software rewrite
mode under Section [9-3-2 Rewriting Software]. If the problem persists, rewrite the software, using a ROM writer.
0000005077.BOOK 16 ページ 2019年5月8日 水曜日 午後3時12分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......