[7-3 Error Code Definitions and Solutions: Codes [1000 - 1999] ]
12
-
chapter 7
BS_07_E
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-3-3
Error Code [1302] (during operation)
1. Error code definition
High pressure fault 1 (Outdoor unit)
2. Error definition and error detection method
1) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor during operation (the first detection), the out-
door stops once, turns to antirestart mode for 3 minutes, and restarts after 3 minutes automatically.
2) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor again (the second detection) within 30 min-
utes after the first stop of the outdoor unit, the outdoor unit stops once, turns to anti-restart mode for 3 minutes, and restarts
after 3 minutes automatically.
3) If the pressure of 3.87MPa [561psi] or higher is detected by the pressure sensor (the third detection) within 30 minutes of the
second stop of the outdoor unit, the outdoor unit will make an error stop, and the error code "1302" will be displayed.
4) If the pressure of 3.78MPa [548psi] or higher is detected more than 30 minutes after the stop of the outdoor unit, the detection
is regarded as the first detection, and the operation described in step 1 above will start.
5) For 30 minutes after the stop of the outdoor unit, preliminary errors will be displayed on the LED display.
6) The outdoor unit makes an error stop immediately when not only the pressure sensor but also the pressure switch detects
4.15
+0,-0.15
MPa [601
+0,-22
psi]
7) Open phase due to unstable power supply voltage may cause the pressure switch to malfunction or cause the units to come
to an abnormal stop.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Hydro unit LEV1 actuation failure -> Cooling
Hydro unit LEV1 actuation failure -> Heating
Perform a cooling or heating operation to check the oper-
ation.
Cooling: Hydro unit LEV1
Heating: Hydro unit LEV1
Refer to the following page(s). [8-8 Troubleshooting LEV,
FCV Problems]
(2)
Closed refrigerant service valve
Confirm that the refrigerant service valve is fully open.
(3)
Short cycle on the indoor unit side
Check the indoor units for problems and correct them, if
any.
(4)
Clogged filter on the indoor unit
(5)
Reduced air flow due to dirty fan on the indoor unit
fan
(6)
Dirty heat exchanger of the indoor unit
(7)
Indoor fan (including fan parts) failure or motor
failure
Rise in high pressure caused by lowered con-
densing capacity in heating operation for (2) - (7).
(8)
Short cycle on the outdoor unit
Check the outdoor units for problems and correct them, if
any.
(9)
Dirty heat exchanger of the outdoor unit
(10)
Outdoor fan (including fan parts) failure, motor
failure, or fan controller malfunction
Rise in discharge temp. by low pressure drawing
for (8) - (10).
Check the fan on the outdoor unit.
Refer to the following page(s). [8-7 Troubleshooting Out-
door Unit Fan Problems]
(11)
Solenoid valve (SV1a) malfunction (The by-pass
valve (SV1a) can not control rise in high pres-
sure).
Refer to the following page(s). [8-6 Troubleshooting Sole-
noid Valve Problems]
(12)
Thermistor failure (TH3, TH7)
Refer to the following page(s). [7-7-2 Error Codes
[5102,5103,5104,5105,5106,5107,5115]]
(13)
Pressure sensor failure
Refer to the following page(s). [8-5-1 Comparing the High-
Pressure Sensor Measurement and Gauge Pressure]
(14)
Failure of the thermistor input circuit and pressure
sensor input circuit on the controller board
Check the temperature and the pressure of the sensor
with LED monitor.
(15)
Thermistor mounting problem (TH3, TH7)
Check the temperature and the pressure of the sensor
with LED monitor.
(16)
Disconnected male connector on the pressure
switch (63H1) or disconnected wire
(17)
Voltage drop caused by unstable power supply
voltage
Check the input voltage at the power supply terminal block
(TB1).
0000004984.BOOK 12 ページ 2019年5月17日 金曜日 午前8時21分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......