[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
42
-
chapter 7
BS_07_E
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-6-22
Error Codes [4235, 4236] Detail Code 125
1. Error code definition
Heatsink overheat protection (Detail code 125) (outdoor unit)
2. Error definition and error detection method
Detection of fan INV heatsink temperature (THHS)
≥
100°C
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems]
7-6-23
Error Code [4230] Detail Code 126
1. Error code definition
DCL temperature fault (Detail code 126)(outdoor unit)
2. Error definition and error detection method
When DCL temperature that equals or exceeds 150
˚
C is detected (applicable to INV37YC only)
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems]
Cause
Check method and remedy
(1)
FAN board fault
Refer to the following page(s).
[8-10-8 Checking the Fan Board Error Detection Circuit at No Load]
[8-10-9 Checking the Fan Board for Damage at No Load]
[8-10-10 Checking the Fan Board for Damage with Load]
(2)
Outdoor unit fan failure
1)
Check the outdoor unit fan for proper operation.
Check the fan motor if problems are found with the operation of the fan.
Refer to the following page(s). [8-10-7 Checking the Fan Motor for Ground
Fault and Coil Resistance Problems]
(3)
Air passage blockage
1)
Check the heatsink and the duct for blockage.
Refer to the following page(s). [8-10-20 Checking the Fan Inverter Heatsink for
Clogging]
(4)
THHS failure
1)
Check the IGBT heatsink for proper mounting.
2)
Check the THHS sensor reading on the LED.
→
Replace the INV board if the THHS value is abnormal.
Cause
Check method and remedy
(1)
Contact failure
Check the connector CNTH on the INV board for proper connection.
(2)
DCL temperature sen-
sor fault
Disconnect the connector (CNTH), and measure the resistance of the DCL temper-
ature sensor. Replace the DCL temperature sensor if the value is abnormal. Refer
to [3-3 Functions of the Major Components of Outdoor Unit].
(3)
INV board failure
Replace the INV board if the problem persists after the operation is resumed.
0000004984.BOOK 42 ページ 2019年5月17日 金曜日 午前8時21分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......