[2-4 M-NET Address Settings ]
4
-
chapter 2
BS_02_E
2
Rest
rict
io
ns
2-4
M-NET Address Settings
2-4-1
Address Settings List
1. M-NET Address settings
(1) Address settings table
The need for address settings and the range of address setting depend on the configuration of the system.
*1. Address setting is not required for a City Multi system that consists of a single refrigerant circuit (with some exceptions).
*2. To set the ME remote controller address to "200", set the rotary switches to "00".
*3. To set the outdoor unit address to "100," set the rotary switches to "50."
*4. Some indoor units have 2 or 3 controller boards that require address settings.
No. 2 controller board address must be equal to the sum of the No. 1 controller board address and 1, and the No.3
controller board address must equal to the No. 1 controller address and 2.
*5. If a given address overlaps any of the addresses that are assigned to other units, use a different, unused address within the
setting range.
Unit or controller
Address setting
range
Setting method
Facto-
ry set-
ting
CITY MULTI in-
door unit
Main/sub unit
00,
01 to 50
*1*5
Assign the smallest address to the main indoor unit in the
group, and assign sequential address numbers to the rest
of the indoor units in the same group.
*4
00
LOSSNAY
00,
01 to 50
*1*5
Assign an arbitrary but unique address to each of
these units after assigning an address to all indoor
units.
00
ME remote con-
troller
Main remote
controller
101 to 150
Add 100 to the smallest address of all the indoor units
in the same group.
101
Sub remote
controller
151 to 200
*2
Add 150 to the smallest address of all the indoor units
in the same group.
MA remote controller
No address settings required. (The main/sub setting must be made if 2
remote controllers are connected to the system.)
Main
CITY MULTI outdoor unit
00,
51 to 99
*1,*3,*5
00
Auxiliary outdoor
unit
Hydro unit
00,
52 to 100
*1
Assign an address that equals the "address of the out-
door unit in the same refrigerant circuit plus 1" to the
unit.
00
System controller
Group remote
controller
201 to 250
Assign an address that equals the sum of the smallest
group number of the group to be controlled and 200.
201
System remote
controller
Assign an arbitrary but unique address within the
range listed on the left to each unit.
ON/OFF re-
mote controller
Assign an address that equals the sum of the smallest
group number of the group to be controlled and 200.
Schedule timer
(compatible
with M-NET)
Assign an arbitrary but unique address within the
range listed on the left to each unit.
202
Centralized
controller
AE-200
000,
201 to 250
Assign an arbitrary but unique address within the
range listed on the left to each unit. The address must
be set to "000" to control the K-control unit.
000
LM adapter
201 to 250
Assign an arbitrary but unique address within the
range listed on the left to each unit.
247
0000004972.BOOK 4 ページ 2019年5月8日 水曜日 午後2時48分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......