[8-2 ME remote Controller Problems ]
BS_08_E
chapter 8 -
9
8 Troub
le
sho
oting Bas
ed on Ob
ser
ved
Sy
mp
toms
8-2-4
"88", "Request denied." Appears on the LCD.
1. Phenomena
"88", "Request denied." appears on the remote controller when the address is registered or confirmed.
2. Cause, check method and remedy
Cause
Check method and remedy
An error occurs when the address is registered or con-
firmed. (common)
1.
A wrong address is set to the unit to be coupled.
(1)
Confirm the address of unit to be coupled.
2.
The transmission line of the unit to be coupled is dis-
connected or is not connected.
(2)
Check the connection of transmission line.
3.
Circuit board failure of the unit to be coupled
(3)
Check voltage of the terminal block for transmission
line of the unit to be coupled.
1)
Normal if voltage is between 17 and 30 VDC.
4.
Improper transmission line work
2)
Check (5) in case other than 1).
Generates at interlocking registration between LOSS-
NAY and the indoor unit
5.
The power of LOSSNAY is OFF.
(4)
Check for the main power of LOSSNAY.
Generates at confirmation of controllers used in the
system in which the indoor units connected to different
outdoor units are grouped
6.
The power of the outdoor unit to be confirmed has
been cut off.
(5)
Check the power supply of the outdoor unit which is
coupled with the unit to be confirmed.
7.
Transmission line is disconnected from the terminal
block for central control system connection (TB7) on
the outdoor unit.
(6)
Check that the transmission line for centralized
control (TB7) of the outdoor unit is not disconnect-
ed.
8.
When the indoor units connected to different outdoor
units are grouped without MELANS, the male power
supply connector is not connected to the female
power supply switch connector (CN40) for the trans-
mission line for centralized control.
(7)
Check voltage of the transmission line for central-
ized control.
9.
The male power supply connectors on 2 or more out-
door units are connected to the female power supply
switch connector (CN40) for the transmission line for
centralized control.
1)
Normal when voltage is between 10V and 30V
10.
In the system to which MELANS is connected, the
male power supply connector is connected to the fe-
male power supply switch connector (CN40) for the
transmission line for centralized control.
2)
Check 8 - 11 described on the left in case other than
1).
11.
Short circuit of the transmission line for centralized
control
0000004986.BOOK 9 ページ 2019年5月9日 木曜日 午後6時22分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......