[5-3 Hydro Unit Control ]
BS_05_E
chapter 5 -
25
5
Cont
rol
(2) Starting the defrost operation
The defrost cycle will start when all of the three conditions (outside temperature, cumulative compressor operation time, and
pipe temperature) under <Condition 1>, <Condition 2>, or <Condition 3> are met.
1) Evaporating temperature (Te)
The defrost cycle will not start if other outdoor units are in the defrost cycle or until a minimum of 10 minutes have passed
since the completion of the last defrost cycle.
If 10 minutes have passed since compressor startup or since the completion of a defrost cycle, a forced defrost cycle can be
started by setting DIP SW4(913) to ON.
Even if the defrost-prohibit timer is set to 90 minutes, the actual defrost-prohibit time for the next defrost cycle is 50 minutes
if the last defrost cycle took 12 minutes.
All units in the heating mode will simultaneously go into the defrost cycle in a system with multiple units. The units that are
not in operation may or may not go into the defrost cycle, depending on the cumulative operation time of their compressors.
(3) Defrost cycle
*The indoor unit fan will stop during defrost.
Condition 1
Condition 2
Condition 3
Outside temperature
(TH7)
-5ºC [23ºF] or above
-5ºC [23ºF] or below
Cumulative compressor
operation time
50 minutes or more
90 minutes or more if the defrost prohibit timer is set to 90.
250 minutes or more
Evaporating tempera-
ture (Te)
The evaporating temperature
has stayed below the tempera-
ture in the table below (Note1)
for 3 minutes
(Te
≤
1.1 × TH7 - 7.5) continued
for 3 minutes or [{1.5 + 0.02 x
(20+TH7)} > 63LS] continued
for 3 minutes
The evaporating temperature
has stayed below the tempera-
ture in the table below (Note1)
for 3 minutes
(E)M200 - 300
(E)M350 - 500
SW4 (915) OFF
-13 ºC
-11 ºC
SW4 (915) ON
-8 ºC
-8 ºC
Outdoor unit fan
Stopped
SV1a
ON
21S4a
OFF
21S4b, 21S4c
OFF
SV2
ON
SV9
ON
SV10,SV11
OFF (Closed)
SV14
*1
*1. Only the EM200 through 450 models have SV14 and SV15.
ON (Open)
SV15
*1
OFF (Open)
LEV1
0 pulses
*2
*2. This value may be greater than 0 pulse depending on the 63LS and TH4 status.
LEV2a
1500 pulses (M200–300), 3000 pulses (M350–500, EM200–500)
LEV2b
3000 pulses (M200–500, EM500), 41 pulses (EM200–450)
LEV2c
3000 pulses (M500, EM500)
LEV4
0 pulses
DIP SW 001-10
ON (Bypass defrost)
OFF (Heat recovery defrost)
Hydro unit
LEV1
41
3000
SV1
ON
OFF
WP1
Normal control
Command value 100%
0000004980.BOOK 25 ページ 2019年5月9日 木曜日 午後6時18分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......