[8-11 Control Circuit ]
BS_08_E
chapter 8 -
67
8 Troub
le
sho
oting Bas
ed on Ob
ser
ved
Sy
mp
toms
3) CMH-WM250 - WM500V-A
YES
YES
NO
NO
A
B
NO
8-12 VDC
Fuse F4 is blown.
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
24-30 VDC
24-30 VDC
24-30 VDC
24-30 VDC
24-30 VDC
YES
NO
24-30 VDC
YES
YES
NO
NO
NO
YES
YES
Fuse F4 is
blown.
Check the voltage at the indoor/outdoor
transmission terminal block (TB3) of outdoor unit.
Check whether the transmission line is disconnected,
check for contact failure, and repair the problem.
Check if the indoor/outdoor transmission line is
not short-circuited, and repair the problem.
Check the wiring between the control board and
power-supply board, and also check connectors CNPW,
CNPS, CN202, and CNINT for proper connections.
Check the wiring between the control board and
power-supply board, and also check connectors CNPW,
CNPS, CN202, and CNINT for proper connections.
Correct wiring problems, and tighten loose connectors.
Correct wiring problems, and tighten loose connectors.
Disconnect CN1 on the noise filter board,
replace F4, and turn on the power supply.
Check the voltage at TB3 after removing
transmission line from TB3.
Check whether the male connector is connected to the
female power supply connector (CN40).
Connected
Check voltage of terminal block for centralized control (TB7).
Check voltage of TB7 by removing transmission line from TB7.
Check the voltage across pins 3 and 4 of CNPW on the control board.
Check the voltage across pins 1 and 2 of CNPW on the control board.
Check the voltage across pins 1 and 2 of CN600 on the control board.
Check the wiring between the control board and
power-supply board, and also check connectors
CN600 and CNDC for proper connections.
Check the wiring between the noise filter board and
power-supply board, and also check connectors
CN1 and CN100 for proper connections.
Fix the wiring and connector
disconnection.
Correct wiring problems, and
tighten loose connectors.
Check for shorted transmission
line or power feed collision for
centralized control.
Replace the control board.
YES
NO
Any problems with wiring or
loose connectors?
Is there a wiring
error or a connector
disconnection?
Check the voltage across pins 4-1 of CNPS on the control board.
YES
Replace the noise filter.
Replace the control board.
Replace the power-supply board.
3.25-3.35 VDC
Check fuse F4 on the noise filter board.
YES
NO
Replace the power-supply board.
Any problems with wiring or
loose connectors?
Any problems
with wiring or loose
connectors?
0000004986.BOOK 67 ページ 2019年5月9日 木曜日 午後6時22分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......