[5-3 Hydro Unit Control ]
26
-
chapter 5
BS_05_E
5
Cont
rol
(4) Recovering from Defrost
The setting of the dip switch 001-10 determines the defrost method (bypass defrost or heat recovery defrost).
As shown in the following flow chart, the bypass defrost may be performed during the heat recovery defrost depending on the
operation status.
Heating
Receiving
"Defrost" signal
from OC
No
Yes
Bypass defrost
ON
OFF
Hydro unit
Dip switch
SW001-10
High pressure heat recovery defrost:
LEV1 = 3000
Pump = Always in operation
Indoor unit FCV during Thermo-ON = Fully open
No
No
No
No
Lower the frequency,
count the No. of freezing.
Freezing is
suspected.
No. of freezing
< 3 times
Yes
Yes
Yes
Receiving
"Defrost" signal
from OC
Recovering from Defrost
Yes
Water temp.<28°C
(DIP SW 002-10: OFF)
Water temp.<20°C
(DIP SW 002-10: ON)
0000004980.BOOK 26 ページ 2019年5月9日 木曜日 午後6時18分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......