[7-3 Error Code Definitions and Solutions: Codes [1000 - 1999] ]
BS_07_E
chapter 7 -
13
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-3-4
Error Code [1302] (at startup)
1. Error code definition
High pressure fault 2 (Outdoor unit)
2. Error definition and error detection method
If the pressure of 0.098MPa [14psi] or lower is registered on the pressure sensor immediately before start-up, it will trigger an
abnormal stop, and error code "1302" will be displayed.
3. Cause, check method and remedy
7-3-5
Error Code [1500]
1. Error code definition
Refrigerant overcharge
2. Error definition and error detection method
An error can be detected by the discharge temperature superheat.
1) If the formula "ToilSH (shell bottom SH) 10°C [50°F]" is satisfied during operation (first detection), the outdoor unit stops,
goes into the 3-minute restart mode, and starts up in three minutes.
2) If the formula "TdSH 10°C [50°F]" is satisfied again within 30 minutes of the fifth stoppage of the outdoor unit (sixth detec-
tion), the unit comes to an abnormal stop, and the error code "1500" appears.
3) If the formula "ToilSH (shell bottom SH) 10°C [50°F]" is satisfied 30 minutes or more after the first stoppage of the outdoor
unit, the same sequence as Item 1) above (first detection) is followed.
4) For 30 minutes after the stop of the outdoor unit, preliminary errors will be displayed on the LED display.
3. Cause, check method and remedy
(18)
Open phase in the power-supply due to improper
power-supply wiring
Refer to item (5) in section [6-1 Read before Test Run].
Cause
Check method and remedy
(1)
Inner pressure drop due to a leakage.
Refer to the following page(s). [8-5-1 Comparing the
High-Pressure Sensor Measurement and Gauge
Pressure]
(2)
Pressure sensor failure
(3)
Shorted-circuited pressure sensor cable due to torn
outer rubber
(4)
A pin on the male connector on the pressure sensor
is missing or contact failure
(5)
Disconnected pressure sensor cable
(6)
Failure of the pressure sensor input circuit on the
controller board
(7)
Open phase in the power-supply due to improper
power-supply wiring
Refer to item (5) in section [6-1 Read before Test
Run].
Cause
Check method and remedy
(1)
Overcharged refrigerant
Refer to the following page(s). [6-3 Evaluating and Adjust-
ing Refrigerant Charge]
(2)
Thermistor input circuit failure on the control board
Check the temperature and pressure readings on the sen-
sor that are displayed on the LED monitor.
(3)
Faulty mounting of thermistor (TH15)
Check the temperature and pressure readings on the
thermistor that are displayed on the LED monitor.
(4)
Outdoor unit LEV2 actuation failure -> Heating
Refer to the following page(s). [8-8 Troubleshooting LEV,
FCV Problems]
0000004984.BOOK 13 ページ 2019年5月17日 金曜日 午前8時21分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......