[5-2 Outdoor Unit Control ]
12
-
chapter 5
BS_05_E
5
Cont
rol
5-2-4
Refrigerant Bypass Control
Bypass solenoid valves (SV1a), which bypass the high- and low- pressure sides, perform the following functions.
(1) Bypass solenoid valve (SV1a) (ON = Open), (SV2) (ON = Open), (SV9) (ON = Open)
Operation
SV1a
ON OFF
When starting-up the compressor of each
outdoor unit
ON for 4 minutes.
After the restoration of thermo or 3 minutes
after restart
ON for 4 minutes.
During cooling or heating operation with the
compressor stopped
Always ON.
Exception: OFF when 63HS1-63LS is 0.2 MPa [29 psi] or less
After the operation has stopped
ON for 3 minutes.
Exception: OFF when 63HS1-63LS is 0.2 MPa [29 psi] or less
During defrost operation
ON
During compressor operation at Fmin fre-
quency in the cooling mode and when the
low pressure (63LS) drops (three or more
minutes after compressor startup)
When low pressure (63LS) drops
below 0.23 MPa [33 psi].
When low pressure (63LS) ex-
ceeds 0.38 MPa [55 psi].
The following conditions are met during the
heating mode: Compressor frequency after
power on is greater than 0.
The low pressure (63LS) drops (One or
more minutes after compressor startup if the
cumulative compressor operation time is
one hour or less; three or more minutes if
the cumulative compressor operation time is
one hour or more)
When the low pressure (63LS)
drops below 0.12 MPa [17 psi]
When the low pressure (63LS) ris-
es above 0.16 MPa [23 psi]
When high pressure (63HS1) rises
When 63HS1 exceeds
3.62 MPa [525 psi]
When 63HS1 is 3.43MPa [497 psi]
or below in 30 seconds
Operation
SV2
ON OFF
During defrost
Always ON
When returning to normal operation after
completion of the defrost cycle
ON for 5 minutes
After 5 minutes have passed
At startup
When TH7<= -20, SV2 stays on for
5 minutes after startup or until the
condition 63HS < 1.96 MPa (284
psi) is met
Other than on the left
Others
Always OFF
Operation
SV9
ON OFF
When high pressure (63HS1) rises during
the heating operation
When 63HS1 exceeds 3.50MPa
[507psi]
When 63HS1 is or below 2.70Mpa
[391psi]
During defrost
Always ON
Others
Always OFF
0000004980.BOOK 12 ページ 2019年5月9日 木曜日 午後6時18分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......