[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
62
-
chapter 7
BS_07_E
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-8-3
Error Code [6600]
1. Error code definition
Address overlap
2. Error definition and error detection method
An error in which signals from more than one indoor units with the same address are received
Detail code 001: Detection of overlapped address in centralized control system
Detail code 002: Detection of overlapped address in indoor unit system
The address and attribute that appear on the remote controller indicate the controller that detected the error.
3. Cause, check method and remedy
7-8-4
Error Code [6601]
1. Error code definition
Polarity setting error
2. Error definition and error detection method
The error detected when transmission processor cannot distinguish the polarities of the M-NET transmission line.
Detail code 001: Detection of polarity setting error in centralized control system
Detail code 002: Detection of polarity setting error in indoor unit system
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Two or more of the following have the same address:
Outdoor units, indoor units, hydro units, LOSSNAY
units, controllers such as ME remote controllers.
<Example>
6600 "01" appears on the remote controller
Unit #01 detected the error.
Two or more units in the system have 01 as their ad-
dress.
Find the unit that has the same address as that of the error
source.
Once the unit is found, correct the address.
Then, turn off the outdoor units, indoor units, hydro
units, and LOSSNAY units, keep them all turned off for
at least five minutes, and turn them back on.
When air conditioning units are operating normally despite
the address overlap error
Check the transmission wave shape and noise on the
transmission line.
Refer to the following page(s). [8-4 Checking Transmission
Waveform and for Electrical Noise Interference]
(2)
Signals are distorted by the noise on the transmission
line.
Cause
Check method and remedy
(1)
No voltage is applied to the M-NET transmission line
that AG-150A/GB-50ADA/PAC-YG50ECA/BAC-
HD150 are connected to.
Check if power is supplied to the M-NET transmission
line of the AG-150A/GB-50ADA/PAC-YG50ECA/BAC-
HD150, and correct any problem found.
(2)
M-NET transmission line to which AG-150A/GB-
50ADA/PAC-YG50ECA/BAC-HD150 are connected
is short-circuited.
(3)
When two or more power supplies are connected to
the M-NET
0000004984.BOOK 62 ページ 2019年5月17日 金曜日 午前8時21分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......