[2-7 Example System with an MA Remote Controller ]
BS_02_E
chapter 2 -
11
2
Rest
rict
io
ns
2-7
Example System with an MA Remote Controller
2-7-1
Single Refrigerant System (Automatic Indoor/Outdoor Address Startup)
(1) Sample control wiring
(2) Cautions
1) ME remote controller and MA remote controller cannot
both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected
to a group of indoor units.
3) A transmission booster is required in a system to which
more than 32 indoor units (26 units if one or more indoor
units of the 200 model or above is connected) are con-
nected.
4) Automatic address setup is not available if start-stop in-
put (CN32, CN51, CN41) is used for a group operation of
indoor units or when multiple indoor units with different
functions are grouped in the same group. Refer to the fol-
lowing page(s). [2-7-2 Single Refrigerant System with
Two or More LOSSNAY Units]
5) For information about connecting two or more LOSSNAY
units to a system, refer to the following page(s). [2-7-2
Single Refrigerant System with Two or More LOSSNAY
Units]
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
2
[AWG16] or larger)
L1 +L2+L3+L4
200m[656ft]
L1 +L2+L11+L12+L13
200m[656ft]
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Maximum overall line length
(0.3 to 1.25mm
2
[AWG22 to 16])
m1
200m [656ft]
m2+m3
200m [656ft]
m4+m5
200m [656ft]
*When connecting PAR-31MAA or MA remote controller,
use sheathed cables with a minimum thickness of 0.3
mm
2
.
IC
TB5
S
TB15
1 2
00
IC
TB5
S
TB15
1 2
00
A B
MA
A B
MA
A B
RC
LC
TB5
S
00
IC
TB5
M1 M2 M1
M2 M1
M2
M1 M2
M1 M2
M1 M2
S
1 2
TB15
IC
TB5
S
TB15
1 2
00
00
IC
TB5
S
TB15
1 2
00
A B
MA
A B
MA
A B
MA
A B
MA
m1
L1
1
m2
L3 L4
L12 L13
m3
m5
m4
Interlock operation with
the ventilation unit
L2
L1
TB3
00
00
TB3
M1 M2
M1 M2
M1 M2
TB7
S
S
OC
HU
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
Group Group
Group
Group
0000004972.BOOK 11 ページ 2019年5月8日 水曜日 午後2時48分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......