[2-7 Example System with an MA Remote Controller ]
BS_02_E
16
-
chapter 2
2
Rest
rict
io
ns
(4) Wiring method
1) Indoor/outdoor transmission line
Same as 2-7-1
Only use shielded cables.
Shielded cable connection
Same as 2-7-1
2) Transmission line for centralized control
Daisy-chain terminals M1 and M2 on the terminal block
for transmission line for centralized control (TB7) on the
outdoor units (OC) in different refrigerant circuits.
a) When connecting TB7, only commence after checking
that the voltage is below 20 VDC.
Only use shielded cables.
Shielded cable connection
Daisy-chain the S terminal on the terminal block (TB7) on
the outdoor units (OC) with the shield wire of the shielded
cable. Short-circuit the earth terminal (
) and the S ter-
minal on the terminal block (TB7) on the outdoor unit
whose power jumper connector is mated with CN40.
3) MA remote controller wiring
Same as 2-7-1
When 2 remote controllers are connected to the sys-
tem
Same as 2-7-1
Group operation of indoor units
Same as 2-7-1
4) LOSSNAY connection
Same as 2-7-2
5) Switch setting
Address setting is required as follows.
(5) Address setting method
Proce-
dures
Unit or controller
Address setting
range
Setting method
Notes
Factory
setting
1
Indoor
unit
Main unit
IC
01 to 50
Assign the smallest ad-
dress to the main unit in
the group.
To perform a group
operation of indoor
units that have differ-
ent functions, desig-
nate the indoor unit in
the group with the
greatest number of
functions as the main
unit.
00
Sub unit
Assign sequential num-
bers starting with the ad-
dress of the main unit in
the same group +1. (Main
unit a1, main unit
a2, main unit ad-
dress +3, etc.)
2
LOSSNAY
LC
01 to 50
Assign an arbitrary but
unique address to each of
these units after assigning
an address to all indoor
units.
None of these ad-
dresses may overlap
any of the indoor unit
addresses.
00
3
MA
remote
control-
ler
Main
remote
controller
MA
No
settings required.
-
Main
Sub
remote
controller
MA
Sub
remote controller
Settings to be made ac-
cording to the remote con-
troller function selection
4
Outdoor unit
OC
51 to 99
Assign the smallest ad-
dress to the outdoor unit
(OC) in the same refriger-
ant circuit.
To set the address to
100, set the rotary
switches to 50.
If the address as-
signed to the hydro
unit overlaps any of
the addresses as-
signed to the outdoor
units, use a different,
unused address in the
specified setting
range.
00
5
Auxiliary
outdoor
unit
Hydro
unit
HU
52 to 100
Assign an address that
equals the "address of the
outdoor unit in the same
refrigerant circuit plus 1" to
the unit.
00
0000004972.BOOK 16 ページ 2019年5月8日 水曜日 午後2時48分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......