[8-1 MA Remote Controller Problems ]
2
-
chapter 8
BS_08_E
8 Troub
le
sho
oting Bas
ed on Ob
ser
ved
Sy
mp
toms
8-1-2
The LCD Momentarily Lights Up and Then Goes Off.
1. Phenomena
When the remote controller operation SW is turned on, the operation status briefly appears on the display, then it goes off,
and the display lights out immediately, and the unit stops.
2. Cause
1) The power for the M-NET transmission line is not supplied from the outdoor unit. For details, refer to the following page(s).[8-
11-2 Troubleshooting Problems with Outdoor Unit Transmission Power Supply Circuit]
2) Short circuit of the transmission line.
3) Incorrect wiring of the M-NET transmission line on the outdoor unit.
Disconnected wire for the MA remote controller or disconnected line to the terminal block.
The indoor transmission line is connected incorrectly to the transmission terminal block for centralized controller (TB7).
The male power supply connectors on the multiple outdoor units are connected to the female power supply switch connector
(CN40).
In the system to which the power supply unit for transmission lines is connected, the male power supply connector is connect-
ed to the female power supply switch connector (CN40) on the outdoor unit.
4) Disconnected M-NET transmission line on the indoor unit side.
5) Disconnected wire between the terminal block for M-NET line (TB5) of the indoor unit and the indoor unit board (CN2M) or
disconnected connector.
3. Check method and remedy
When 2) and 3) above apply, check code 7102 will be displayed on the self-diagnosis LED.
YES
YES
YES
YES
NO
NO
NO
NO
Same symptom for all units in a
system with one outdoor unit?
Check the
self-diagnosis LED
Check item 1) in the
"Cause" column.
Check items 2) and 3)
in the "Cause" column.
Check item 4) in the
"Cause" column.
Measure voltages of the
terminal block for transmission
line (TB5) on the indoor unit.
17 - 30V?
Check item 5)
in the "Cause" column.
Error found?
Indoor unit board or
MA remote controller failure
Correct the error.
Is the error code 7102
displayed?
0000004986.BOOK 2 ページ 2019年5月9日 木曜日 午後6時22分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......