[5-2 Outdoor Unit Control ]
16
-
chapter 5
BS_05_E
5
Cont
rol
(2) Defrost operation
Compressor frequency
Model
Compressor frequency
Standard
M200 model
100 Hz
M250-300 models
100 Hz
M350-400 models
121 Hz
M450 model
147 Hz
M500 model
147 Hz
High COP
EM200-300 models
100 Hz
EM350 model
121 Hz
EM400-450 models
147 Hz
EM500 model
147 Hz
Outdoor unit fan
Stopped
SV1a
ON
21S4a OFF
21S4b, 21S4c
OFF
SV2
ON
SV9
ON
SV10,SV11
OFF (Closed)
SV14
*1
*1. Only the EM200 through 450 models have SV14 and SV15.
ON (Open)
SV15
*1
OFF (Open)
LEV1 0
pulses
*2
*2. This value may be greater than 0 pulse depending on the 63LS and TH4 status.
LEV2a
1500 pulses (M200–300)
3000 pulses (M350–500, EM200–500)
LEV2b
3000 pulses (M200–500, EM500)
41 pulses (EM200–450)
LEV2c
3000 pulses (M500, EM500)
LEV4
0 pulse
0000004980.BOOK 16 ページ 2019年5月9日 木曜日 午後6時18分
Summary of Contents for City Multi CMH-WM250V-A
Page 1: ......
Page 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Page 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Page 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Page 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Page 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Page 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Page 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Page 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Page 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Page 436: ......