IM-790
Page 1
Installation and Maintenance Manual
Group:
Applied Systems
Part Number: IM790
Date: June 2004
Ultraviolet Lights on
Daikin
Applied Rooftop Systems and Rooftop Air Handlers
Models RPS/RDT/RFS/RPE/RDE/RDS/RAH
© 2004
Daikin Applied
Page 1: ...tion and Maintenance Manual IM 790 Group Applied Systems Part Number IM790 Date June 2004 Ultraviolet Lights on Daikin Applied Rooftop Systems and Rooftop Air Handlers Models RPS RDT RFS RPE RDE RDS R...
Page 2: ...r are fac tory installed on every door that allows a direct line of sight to the UV lamps when opened These switches are designed to prevent UV exposure when cabinet doors are opened and must not be d...
Page 3: ...r power disconnect switches are closed To turn the lights off disconnect power to the entire unit or open system switch S1 The normally open disconnect switches are wired in series in a circuit that s...
Page 4: ...llow bulbs to cool for 5 minutes before handling 2 Grasp body of bulb firmly at each end 3 Rotate bulb 90 degrees in either direction 4 Remove bulb 5 Reverse process to install replacement bulb 6 Wipe...
Page 5: ...aikin Applied www DaikinApplied com 800 432 1342 This document contains the most current product information as of this printing For the most up to date product information please go to www DaikinAppl...