IM-790

  Page 3

Operation

Refer to the Wiring Schematic below. 115 VAC power for the 
UV lights is provided by control circuit transformer T1. The 
lights operate whenever the unit is powered, system switch S1 
is closed, and all doors with door power disconnect switches 
are closed. To turn the lights off, disconnect power to the entire 
unit, or open system switch S1. 

The normally open disconnect switches are wired in series in a 
circuit that supplies 24VAC to the coil of relay R45. When all 
doors are closed, relay R45 is energized, and its normally open 
contacts (in series with system switch S1) provide 115VAC to 
the UV lights.

Figure 2.  Typical Ultraviolet Light Wiring Schematic 