
MEP 660 - Trouble shooting Manual
Doc No.: IM – 51
Rev.2.0
Print: October 2008
71
PARAMETER
DESCRIPTION
FAULT CODE
1069
FAULT MESSAGE REV-F Aux. Contact ckt. Open. Run Auto/manual Test.
RESTRICTIONS
Forward Motoring and Forward Dynamic Brake Prohibited
ALARM BELL
30 seconds
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
RECOVERY
Automatic when the REV-F Auxiliary contact circuit is closed.
PROBABLE
CAUSES
1. Bad contact of REV-F auxiliary contact.
2. Disconnected wires at auxiliary contacts / open circuited wiring.
3. Defective digital input card.
FAULT
ISOLATION
1. Ensure Reverser is in forward direction. If not operate manually.
2. Check the status of the Green LED 14 on the digital input card in
slot 10.
3. If the Green LED is not glowing:
A. Auxiliary contact is bad. Clean/adjust the contact and check.
B. Check supply voltage at incoming terminal (wire No. 51) with
respect to locomotive 4 wire.
C. If supply is zero, check the continuity of 51-wire loop.
A. If the supply voltage is more than 65V, check supply between
wire no. RVFFB and locomotive 4 wire.
D. If the supply voltage is more than 65V,
a) Check the slackness of the connector of the cable ID: AU at
MEP660. If slack tighten the connector.
b) Check the continuity of the wire REFFB, from the reverser
aux. Contact to connector of cable ID: AU, Pin – R. If
necessary replace the cable.
4. If green LED 14 is glowing but the corresponding yellow LED is not
glowing, then the digital input card is defective. Replace the card
and check up.