MEP 660 - Trouble shooting Manual
Doc No.: IM – 51
Rev.2.0
Print: October 2008
265
PARAMETER
DESCRIPTION
FAULT CODE
2516
FAULT MESSAGE R1 Stuck Closed in Auto Test
RESTRICTIONS
--
ALARM BELL
--
RESET LEVEL
--
FAULT
RECOVERY
--
PROBABLE
CAUSES
1. Defective R1 contactor
2. Defective wiring.
FAULT
ISOLATION
Most probably this fault can be logged due to delayed drop out of the
contactor. Adjustment of Pick up / drop out values of R1 contactor
could solve the problem.
1. Check the status of the R1 contactor.
2. If the R1 contactor is in energized position, check the supply across
the operating coil.
3. If the voltage is zero and still R1 is energised, then the R1 it self is
defective. (Due to magnatisation of core). Replace the contactor.
4. If voltage is more than 65V, the digital output card MLSD16 has
gone defective. Replace the card and check up.
After adjustment / replacement o contactor perform once again auto
test and confirm that the contactor is functioning normal.
PARAMETER
DESCRIPTION
FAULT CODE
2517
FAULT MESSAGE R2 Stuck Closed in Auto Test
RESTRICTIONS
--
ALARM BELL
--
RESET LEVEL
--
FAULT
RECOVERY
--
PROBABLE
CAUSES
1. Defective R2 contactor.
2. Defective MLSD16 card.
FAULT
ISOLATION
Most probably this fault can be logged due to delayed drop out of the
contactor. Adjustment of Pick up / drop out values of R2 contactor
could solve the problem.
1. Check the status of the R2 contactor.
2. If the R2 contactor is in energized position, check the supply across
the operating coil.
3. If the voltage is zero and still R2 is energised, then the R2 it self is
defective. (Due to magnatisation of core). Replace the contactor.
4. If voltage is more than 65V, the digital output card MLSD16 has
gone defective. Replace the card and check up.
After adjustment / replacement o contactor perform once again auto
test and confirm that the contactor is functioning normal.