MEP 660 - Trouble shooting Manual
Doc No.: IM – 51
Rev.2.0
Print: October 2008
185
PARAMETER
DESCRIPTION
FAULT CODE
1181
FAULT MESSAGE WS EEPROM Faulty. Default CFG record loaded
RESTRICTIONS
Warning only
ALARM BELL
--
RESET LEVEL
High, Manual
FAULT
RECOVERY
--
PROBABLE
CAUSES
This fault will be logged while switching ON power supply. Loco can
work with default parameters.
FAULT
ISOLATION
--
PARAMETER
DESCRIPTION
FAULT CODE
1182
FAULT MESSAGE WS Analogue DB Power Supply FAULTY
RESTRICTIONS
Warning only
ALARM BELL
--
RESET LEVEL
MEDIUM, Manual
If the fault condition is still present when cleared manually, the fault
will be generated again.
FAULT
RECOVERY
Automatic when the WS analogue DB power supply is detected to
normal.
PROBABLE
CAUSES
Most probably this fault accompany with associated sensors
(Connected to the ADB2) faulty.
1. Defective Analog distribution box.
2. Defective wiring.
FAULT
ISOLATION
1. Replace the ADB and check up
2. Replace the cable ID:I and check up.
3. Check for disconnected wires at backside TB for the wire No. PSH2.
4. Check the continuity of wire PSH2 from TB to the Cable connector
(Cable ID:I Pin – C). If necessary replace the cable.
5. Check the status of the Green LED 5 on the digital input card
MDIP16 in slot No. 12.
6. If the green LED glowing and corresponding Yellow LED 5 is not
glowing the digital input card MDIP16 is defective. Replace and
check up.