MEP 660 - Trouble shooting Manual
Doc No.: IM – 51
Rev.2.0
Print: October 2008
24
PARAMETER
DESCRIPTION
FAULT CODE
1019
FAULT MESSAGE CEB Breaker OFF.
RESTRICTIONS
No restrictions, only indication.
ALARM BELL
Continuous ON
RESET LEVEL
Low, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
RECOVERY
Automatic when CEB breaker is switched ON.
PROBABLE
CAUSES
1. Crank Case Exahauster Motor is not getting supply due to CCEB
tripped or switched OFF.
2. Crankcase Exhauster Breaker Feed Back (CEB FB) status is low as
sensed by MEP-660.
FAULT
ISOLATION
1. If Breaker is in tripped/OFF position, reset/switch ON the breaker.
2. The high level status of the Crankcase Exhauster Breaker Feed Back
is indicated by 7 Numbered Green and Yellow LEDs on digital input
card MDIP-16 in slot No. 13.
3. With CEB in ON position, CCEM fail indication LEDs on both control
desks should be OFF. Both 7 numbered Green and Yellow LEDs on
the Digital Input card in slot 13 should be ON.
A. If the indications LEDs on both the control desks are ON, then
the breaker is defective and the CCEM is not working. Replace
the breaker.
B. If 7 numbered Green LED is OFF on digital input card in slot 13,
then wiring from CEB breaker to MEP-660 open circuited. Check
and replace wiring.
C. If 7-numberED Green LED is ON and 7-numbered Yellow LED is
OFF, the digital input card in slot 13 is defective. Replace and
check.