MEP 660 - Trouble shooting Manual
Doc No.: IM – 51
Rev.2.0
Print: October 2008
11
PARAMETER
DESCRIPTION
FAULT CODE
1008
FAULT MESSAGE Control Circuit Ground Fault.
RESTRICTIONS
Cranking prohibited.
ALARM BELL
Continuous ON
RESET LEVEL
Medium, Manual
After manual reset if the fault still present, the fault will be generated
again.
FAULT
RECOVERY
Automatic when the control circuit negative to ground leakage current
value is reduced below the set limit and 15 seconds lapsed with Master
Handle in IDLE. Automatic Fault reset is permitted for 3 times in an
hour and after that manually reset is required.
PROBABLE
CAUSES
1. Any control circuit wiring is grounded.
2. Any equipements like dust blower motors, sander coils, lighting
circuit etc. connected in control circuits are having low / zero
insulation resistance value.
FAULT
ISOLATION
1. Identify the control circuit having low/zero Insulation Resistance
(IR) value.
2. Isoalte the low insulation either replacing the equipement or by
insulating the grounded wires.
Note:
This fault is logged during cranking only.