MEP 660 - Trouble shooting Manual
Doc No.: IM – 51
Rev.2.0
Print: October 2008
28
backside TB.
4. If voltage is available on any of the above wires, Disconnect the
bunch wires and identify which lead is getting wrong supply and
rectify.
5. If no voltages are found on the above wires,
A. Operate Master Handle to Motoring position (Notch 1) on control
stand 1. Check voltages on TL17 and TL23.
a) If voltage is >35V on any of the two wires, then repeat the
step 4.
B. Operate the Master Handle to OFF position (Dynamic Brake set
up). Check Voltage on TL6.
a) If Voltage is >35V on TL6, then repeat step 4.
C. Operate the Master Handle to Dy. Brake position. Check Voltage
on TL6.
a) If voltage is > 35V on TL6, then repeat step 4.
D. Move the Master Handle to IDLE position.
E. Rpeat checks from A to D on control stand 2.