Goodrive350-19 series VFD for crane
Function parameter list
-261-
Function
code
Name
Description
Default
Modify
Y,
RO1, RO2
Output frequency
Set
frequency
Detection amplitude
Time t
Time t
Setting range: 0.00Hz
(Max. output
frequency)
P08.37
Enabling
energy-consumpti
on braking
0x00
–0x11
Ones place:
0: Disable
1: Enable
Tens place:
0: Disable braking short-circuit protection
1: Enable braking short-circuit protection
Braking short-circuit protection is disabled for
22kW and lower VFD models by default.
0x01
○
P08.38
Energy-
consumption
braking threshold
voltage
The function code is used to set the starting bus
voltage of energy consumption braking. Adjust
this value properly to achieve effective braking
for the load. The default value varies depending
on the voltage class.
Setting range: 200.0
–2000.0V
For 220V:
380.0V
For 380V:
700.0V
For 660V:
1120.0V
○
P08.39
Cooling-fan
running mode
0: The fan runs with the VFD; the fan stops 1
minute after the VFD stops.
1: Permanent running after power-on
2: Run mode 2
0
○
P08.40
PWM selection
0x0000
–0x1121
Ones place: PWM mode selection
0: PWM mode 1, 3PH modulation and 2PH
modulation
1: PWM mode 2, 3PH modulation
Tens place: PWM low-speed carrier frequency
limit
0x1101
◎