Goodrive350-19 series VFD for crane
Function parameter list
-365-
Function
code
Name
Description
Default
Modify
1:1
1:2
1:4
Note: The suspension ratio is related to the
pulley through which the steel rope goes.
P93.11
Rope length
compensation
Rope length to compensate the distance from
the center of gravity of the weight to the hook.
0.00m
–50.00m
0.00m
○
P93.12
Cable diameter To measure heights correctly in closed-loop
mode, the actual running distance of the motor
is calculated by using the encoder pulse count.
Before first running, the upward limit position
must be calibrated.
The procedure for first running is as follows:
Set the upward limit position terminal, for
example, P05.05=64. Then the HDI terminal
functions as the upward limit position input.
If internal measurement (motor encoder) is
enabled, set
=1.
Start the tower crane to run upward and stop at
the upward limit position.
Record the values of
(Initial turns of drum
winding) and
(Initial diameter of
drum/pulley diameter).
In open/closed loop mode, if external
measurement (HDI) is enabled, set
=2.
Start the tower crane to run upward and stop at
the upward limit position.
setting range: 0.1
–100.0mm
setting range: 1
–200
10.0
○
P93.13
Per-layer turns of
drum winding
30
○
P93.14
Initial turns of
drum winding
0
○
P93.15
Initial diameter of
drum/pulley
diameter
600.0
◎