Goodrive350-19 series VFD for crane
Function parameter list
-347-
Function
code
Name
Description
Default
Modify
P91.20
Load limit T2 in
stepped speed
limit upward
running
limit parameters for upward running and for
downward running are set separately and can
be adjusted according to the actual situation.
When the detected load (open-loop output
current or closed-loop output torque) exceeds
the limited value, the running frequency must be
lower than the set restricted frequency.
For example, during motor upward running,
when the detected load is greater than
the frequency is restricted to
the set frequency is less than
, the
running frequency is the set frequency). When
the detected load is greater than
less than
), the frequency is restricted to
The detected load values in open/closed loop
state have deviation. During the open/closed
loop switchover process, the load limit value can
be adjusted through
For example, when the same load is carried
upward and tested, if
P19.11
=50.0% in
closed-loop state and
P19.11
=55.0% in
open-loop state, there is a difference of 5%. In
the actual use, after setting closed-loop
parameters, if you need to switch to the
open-loop state, you only need to set
5.0% (0 in closed-loop state), and you do not
need to modify
The situation of downward running is similar and
therefore you only need to set parameters
related to downward running.
Note: The heavy load speed limit frequency
cannot be lower than
setting range: 0.0%
–150.0% (Open-loop
output current is relative to the motor rated
45.0%
○
P91.21
Restricted
frequency f2 in
stepped speed
limit upward
running
75.00Hz
○
P91.22
Load limit T3 in
stepped speed
limit upward
running
25.0%
○
P91.23
Restricted
frequency f3 in
stepped speed
limit upward
running
100.00Hz
○
P91.24
Load limit
adjusted gain in
stepped speed
limit upward
running
0.0%
○
P91.25
Torque limit
adjusted gain in
stepped speed
limit downward
running
0.0%
○
P91.26
Load limit T1 in
stepped speed
limit downward
running
55.0%
○
P91.27
Restricted
frequency f1 in
stepped speed
limit downward
running
50.00Hz
○