Goodrive350-19 series VFD for crane
Function parameter list
-212-
Function
code
Name
Description
Default
Modify
Output frequency f
Time t
fmax
t1
t2
2: Slewing application mode
Note: When the function parameter is set to
1, you also need to set
P01.06
Time of starting
segment of ACC S
curve
The curvature of S curve is determined by the
ACC range and ACC/DEC time.
Output frequency f
Time t
t1
t2
t3
t4
t1=P01.06
t2=P01.07
t3=P01.27
t4=P01.28
Setting range: 0.0
–50.0s
0.1s
◎
P01.07
Time of ending
segment of ACC S
curve
0.1s
◎
P01.08
Stop mode
0: Decelerate to stop. After a stop command
takes effect, the VFD lowers output frequency
based on the DEC mode and the defined DEC
time; after the frequency drops to the stop speed
), the VFD stops.
1: Coast to stop. After a stop command takes
effect, the VFD stops output immediately; and
the load coasts to stop according to mechanical
inertia.
0
○
P01.09
Starting frequency
of DC braking for
stop
Starting frequency of DC braking for stop:
During the deceleration to stop, the VFD starts
DC braking for stop when running frequency
reaches the starting frequency determined by
P01.09.
Wait time before DC braking: The VFD blocks
the output before starting DC braking. After this
wait time, DC braking is started so as to prevent
overcurrent caused by DC braking at high
0.00Hz
○
P01.10
Demagnetization
time
0.00s
○
P01.11
DC braking
current for stop
0.0%
○
P01.12
DC braking time
for stop
0.00s
○