Goodrive350-19 series VFD for crane
Basic operation guidelines
-181-
Setting
Function
Description
78
Graded reference terminal
2
Terminal
1
Terminal
2
Terminal
3
Terminal
4
Terminal
5
Speed
setting
OFF
OFF
OFF
OFF
OFF
Graded
setting 0
ON
OFF
OFF
OFF
OFF
Graded
setting 1
ON
ON
OFF
OFF
OFF
Graded
setting 2
ON
ON
ON
OFF
OFF
Graded
setting 3
ON
ON
ON
ON
OFF
Graded
setting 4
ON
ON
ON
ON
ON
Graded
setting 5
79
Graded reference terminal
3
80
Graded reference terminal
4
81
Graded reference terminal
5
82
Upward DEC limit position
When the terminal is valid, the VFD enters the upward slow
speed area and runs at the frequency specified by P91.35.
83
Downward DEC limit
position
When the terminal is valid, the VFD enters the downward
slow speed area and runs at the frequency specified by
P91.35.
84
Light load speed boost
signal
When P91.08=5, the terminal command is valid, light load
speed boost is performed.
85
Brake detection
When the terminal command is valid, brake detection is
performed.
86
Valid signal of PTC
overtemperature
Supporting only the terminalS8 of EC-IO502-00. When
receiving this signal, the PTC overtemperature alarm or fault
is reported.
87
Position synchronization
pulse counting reset
The position synchronization pulse counter status is
cleared.
88
Switchover between
motors 1 and 3
When the function is enabled, you can realize switchover
control of two motors.
89
Anti-snag protection input
When the terminal command is valid, the VFD stops with the
torque specified by P92.27 within the time specified by
P92.28.
90
Enabling anti-sway
When the terminal command is valid, the anti-sway function
is enabled.
Related parameter list:
Function
code
Name
Description
Default
P05.00
HDI input type
0x00
–0x11
Ones place: HDIA input type
0x00