Goodrive350-19 series VFD for crane
Basic operation guidelines
-165-
Function
code
Name
Description
Default
P01.04
DC braking time before start 0.00
–50.00s
0.00s
P01.05
ACC/DEC mode
0: Linear
1: S curve
Note: If mode 1 is selected, it is required to
set P01.07, P01.27 and P01.08 accordingly.
0
P01.08
Stop mode
0: Decelerate to stop
1: Coast to stop
0
P01.09
Starting frequency of DC
braking for stop
0.00Hz
–P00.03 (Max. output frequency)
0.00Hz
P01.10
Wait time before DC braking
for stop
0.00
–50.00s
0.00s
P01.11
DC braking current for stop 0.0
–100.0%
0.0%
P01.12
DC braking time for stop
0.00
–50.00s
0.00s
P01.13
FWD/REV running
deadzone time
0.0
–3600.0s
0.0s
P01.14
FWD/REV running switching
mode
0: Switch at zero frequency
1: Switch at the starting frequency
2: Switch after the speed reaches the stop
speed with a delay
0
P01.15
Stop speed
0.00
–100.00Hz
0.50 Hz
P01.16
Stop speed detection mode
0: Detect by the set speed (unique in space
voltage vector control mode)
1: Detect by the feedback speed
1
P01.18
Terminal-based running
command protection at
power-on
0: The terminal running command is invalid
at power-on
1: The terminal running command is valid at
power-on
0
P01.19
Action selected when
running frequency less than
frequency lower limit (valid
when frequency lower limit
greater than 0)
0: Run at the frequency lower limit
1: Stop
2: Sleep
0
P01.20
Wake-up-from-sleep delay 0.0
–3600.0s (valid when P01.19 is 2)
0.0s
P01.21
Power-off restart selection
0: Disable
1: Enable
0
P01.22
Wait time for restart after
power-off
0.0
–3600.0s (valid when P01.21 is 1)
1.0s