Goodrive350-19 series VFD for crane
Basic operation guidelines
-184-
Setting
Function
Description
7
Frequency level detection FDT2 (Refer to the descriptions for P08.34
–P08.35.)
8
Frequency reached
(Refer to the description for P08.36.)
9
Running in zero speed
The ON signal is output when the VFD output
frequency and reference frequency are both zero.
10
Upper limit frequency reached
The ON signal is output when the running frequency
reaches upper limit frequency.
11
Lower limit frequency reached
The ON signal is output when the running frequency
reached lower limit frequency.
12
Ready for running
Main circuit and control circuit powers are
established, the protection functions do not act;
when the VFD is ready to run, output ON signal.
13
Pre-exciting
The ON signal is output during pre-exciting of the
VFD.
14
Overload pre-alarm
The ON signal is output when the pre-alarm time
elapsed based on the pre-alarm threshold; see
P11.08
–P11.10 for details.
15
Underload pre-alarm
The ON signal is output when the pre-alarm time
elapsed based on the pre-alarm threshold. For
details, see the descriptions for P11.11
–P11.12.
16
Simple PLC stage completed
When the present state of the simple PLC is
completed, it outputs a signal.
17
Simple PLC cycle completed
When a single cycle of the simple PLC is completed,
it outputs a signal.
18
Set counting value reached
The ON signal is output when the set counting value
is reached.
19
Designated counting value
reached
The ON signal is output when the designated
counting value is reached.
20
External fault is valid
The ON signal is output when an external fault is
valid.
22
Running time reached
The ON signal is output when the running time is
reached.
23
Modbus communication
virtual terminal output
A signal is output based on the value set through
Modbus communication. When the value is 1, the
ON signal is output; when the value is 0, the OFF
signal is output.
24
PROFIBUS/CANopen/DeviceNet
communication virtual terminal
output
A signal is output based on the value set through
PROFIBUS/CANopen/DeviceNet communication.
When the value is 1, the ON signal is output; when