Goodrive350-19 series VFD for crane
Function parameter list
-356-
Function
code
Name
Description
Default
Modify
setting range: 0.0%
–180.0% (of the
motor rated torque)
setting range: 0.00Hz
–20.00Hz
setting range: 0.0s
–30.0s
setting range: 0
–20000
P92.12
Enabling
PT100/PT1000
temperature
detection
0x00
–0x11
Ones place: whether to enable PT100
temperature detection
0: Disable
1: Enable
Tens place: whether to enable PT1000
temperature detection
0: Disable
1: Enable
0x00
◎
P92.13
Enabling
PT100/PT1000
disconnection
detection
0x00
–0x11
Ones place: whether to enable PT100
disconnection detection
0: Disable
1: Enable
Tens place: whether to enable PT1000
disconnection detection
0: Disable
1: Enable
0x00
◎
P92.14
PT100
overtemperature
protection point
0.0
–150.0°C
120.0°C
○
P92.15
PT100
overtemperature
pre-alarm point
0.0
–150.0°C
100.0°C
○
P92.16
PT1000
overtemperature
protection point
0.0
–150.0°C
120.0°C
○
P92.17
PT1000
overtemperature
pre-alarm point
0.0
–150.0°C
100.0°C
○
P92.18
PT100/PT1000
calibrated
50.0
–150.0°C
120.0°C
○