Goodrive350-19 series VFD for crane
Function parameter list
-206-
parameters. Incorrect parameter setting may cause operation exceptions or even damage to the
VFD.) If password protection is not in locked state, you can change the password any time. You
to 0 to cancel the user password. When
is set to a non-zero value during
power-on, parameters are prevented from being modified by using the user password function.
When you modify function parameters through serial communication, the user password
protection function is also applicable and compliant with the same rule.
P00 group
––Basic functions
Function
code
Name
Description
Default
Modify
P00.00
Speed control
mode
0: Sensorless vector control (SVC) mode 0
1: Sensorless vector control (SVC) mode 1
2: Space voltage vector control mode
3: Closed-loop vector control mode
Note: Before using a vector control mode (0,
1, or 3), enable the VFD to perform motor
parameter autotuning first.
2
◎
P00.01
Channel of
running
commands
0: Keypad
1: Terminal
2: Communication
0
○
P00.02
Communication
mode of running
commands
0: Modbus
1: PROFIBUS/CANopen/DeviceNet
2: Ethernet
3: EtherCAT/Profinet
4: Programmable expansion card
5: Wireless communication card
6: 216 communication card
Note: The options 1, 2, 3, 4, 5, and 6 are
add-on functions and are available only
when corresponding expansion cards are
configured.
0
○
P00.03
Max. output
frequency
Used to set the max. output frequency of the
VFD. Pay attention to the function code because
it is the foundation of the frequency setting and
the speed of acceleration (ACC) and
deceleration (DEC).
Setting range: Max (
, 10.00)
–150.00Hz
50.00Hz
◎
P00.04
Upper limit of
running frequency
The upper limit of the running frequency is the
upper limit of the output frequency of the VFD,
which is lower than or equal to the max. output
50.00Hz
◎