Using a modulating dehumidifier:
The dehumidification signal is calculated based on the curve indicated below:
H
142
143
100
0
% dehum
CO
2
167
168
165
0
Val_damper
164
141
/ 2
H
100
0
142
% hum
141
/ 2
143
H
142
143
100
0
% dehum
141
/ 2
H
100
0
142
% hum
141
/ 2
143
WDS
WDS
WUS
WUS
H: value of the humidity detected by the internal or remote humidity sensor
WDS: dehumidification mode setpoint
% dehum.: theoretical value percentage of dehumidification
142
: humidity setpoint
141
: humidity neutral zone
143
: humidity proportional band
Settings for dehumidification with modulating dehumidifier:
- select the type of dehumidification with modulating dehumidifier
007
=1,
- define the modulating dehumidifier output
030
=11 (AO1) or
031
=11 (AO2) or
032
=11 (AO3) ,
- turn on dehumidification
- with an internal humidity sensor
139
=1 or
139
=3 only in cooling (AHU-xxxxH1 models only)
- or with a remote humidity sensor
139
=2 or
139
=4 only in cooling,
023
=6 (0..10 V humidity input) and put the JP1
jumper in the “3-2” position,
- humidity neutral zone
141
,
- humidity setpoint
142
,
- humidity proportional band
143
,
- humidity integral time
144
.
Control is carried out on the dehumidification operating setpoint WDS =
142
+ (
141
/2) and is proportional if
144
=0 or propor-
tional integral if
144
≠0.
If the signal applied to the dehumidifier is not equal to 0, the
icon is displayed.
Note: If the frost protection (with
188
=1), condensation alarm or steady ventilation are activated, dehumidification is shut down.